Model | OL6000E |
Capacity(VA/W) | 6000VA / 5400W |
Typology | Online (Double Conversion) |
Form Factor | Tower |
Energy-Saving Technology | Yes, ECO Mode Efficiency > 95% |
Input | |
Voltage Range | 120~139Vac for 0~25% Load 140~159Vac for 0~50% Load 160~179Vac for 0~75% Load 180~280Vac for 0~100% Load |
Frequency Range | 40~70Hz |
Input Plug Type | (1) Terminal Block |
Output | |
Voltage Range | Pure Sinewave at 200, 208, 220, 230, 240Vac (Configurable) ±2% |
Frequency Range | 50 / 60Hz (Auto-Sensing or Configurable) ±0.25Hz |
Transfer Time (Typical) | 0ms |
Overload Protection | Line Mode:105~125% Load for 1 min, 126~150% Load for 10 secs Battery Mode:105~130% Load for 10 secs, 131~150% Load for 2 secs |
Short Circuit Protection | UPS Output Cut Off Immediately or Input Fuse/Circuit Breaker Protection |
Surge Protection and Filtering | |
Lightning / Surge Protection | Yes |
DSL/Phone/Fax/Modem protection | RJ11/RJ45(One In/One Out) |
Short Circuit Protection | UPS Output Cut Off Immediately |
Physical | |
Receptacles | (8) IEC C13, (2) IEC C19, (1) Terminal Block |
Maximum Dimensions (H x W x D) (mm) | 600 x 265 x 660 |
Weight(kg) | 95(Battery included) |
Battery | |
Sealed Maintenance Free Lead Acid Battery | 12V / 7.2AH x 20 |
Hot-Swappable | Yes |
Typical Recharge Time | 4 Hours |
Runtimes | |
Half-load / Full-load (mins) | 15.8 / 5.3 |
Status Indication | |
Indicators | Power On, Line Mode, Battery Mode, Bypass Mode, Fault, Replace Battery |
Audible Alarms | Battery Mode, Battery Low, Overload, UPS Fault, Replace Battery |
Multi-Function LCD Readout | Yes |
Communication | |
Power Management Software | PowerPanel® Business Edition |
Management | |
Self-Test | Yes |
Auto-Charge/Auto-Restart | Yes |
Auto-Overload Recovery | Yes |
Cold Start(DC Start) | Yes |
COM Interface | (1) Serial Port (RS232), (1) USB Port, (1) Remote Control Port, (1) Relay Out, (1) EPO, (1) Backfeed |
SNMP/HTTP Capable | Optional |